 GENERAL type POWER RELAY : KSP-402


    KSP-402                                                                                       
   


-  KSP-402  -


Shape / Dimension drawing -


    Coil Raiting

Rating
volatage(v)

Rating current
(mA)
Coil resistance
(Ω)
Operation
voltage(V)
Return
voltage(V)
Max. allowable
voltage(V)
AC
24
410
17

below 80%

above 30%
110%
110
96
320
220
48
1,200
DC
12
210
51
above 10%
24
105
200
48
50
1,150
110
26.5
3,900

    Contact Raiting

Item / Load

Resistive load
(cos∮ = 1)

Inductive load
(cos∮ = 0.4 L/R = 7ms)

Rated load

AC 110V, 30A
DC 24V, 15A

AC 110V, 20A
DC 24V, 7.5A

Carry current

30A

Max.switching
capacity

AC 500VA, DC 250V

Max.switching
current

30A


    Performance Summary
Item
Performance
Contact resistance
  below 50mΩ (initial value)
Insulation resistance
  above 100MΩ(DC 500V Meg)
Withstand voltage
  between contacts : AC 1000V / 1min
  between charging part : AC 1500V / 1min
  and non - charging part : AC 1500V / 1min
Lift time
  mechanical : above 3,000,000 times
  electrical : above 500,000 times
Power consumption
  for AC : about 9.6VA
  for DC : about 2.5W
Operating time
  below 50ms
Return time
  below 50ms
Withstand vibration
  10~55Hz double amplitude 1.5mm
Withstand impact
  80G
Max. switching frequency
  mechanical : 20times / min
  electrical : 20times / min
Ambient temperature
  -5℃ +40℃
Weight
  about 270g