GENERAL type FLOATLESS
SWITCH : KDFS-8PC
|
|
- Use when toneed control of liquid surface
Multi-Purpose for purifying water to be used for
agficulture. sewage and dirty water
treaments. |
|
- Easy to install due to small in size and
light in weight. |
|
- Voltge of electrode(2 voltage) is
operated by AC
12V. |
Item |
DFS-8PC |
Rating voltage |
AC 100V, AC
220V |
Voltage varlation range |
AC 110V/220C
50/60Hz ±10% within |
Voltage between
electrodes |
AC 12V (2nd
voltage) |
Power consumption |
about3.2VA |
Operating resistance |
about
4KΩ |
Return resistance |
about below
15KΩ |
Response time |
In operating
below 80ms, In return below 160ms
|
Ambient temperature |
-10 ~
+50℃ |
Insulation resistance |
below 100MΩ
(at DC500V Meg) |
Max. sense distance |
below
1km |
Relay output contact
capacity |
Ac 250V
2.5A, Ac 110V 5A (Resistive load)
|
Relay lifetime |
Electrical :
above 500,000 times Mechanical : above
5,000,000
times |
|
|
※ Please be sure E3
terminal to be earthed |
※ Please
be sure E3 terminal to be
earthed |
KDFS-8PC
(56) Wifing Diagram
Using example in water
supply |
Using example in water
drainage |
|
|
- Conevt to designated terminal
after checking in-put
electricity. - After distributing
wires, plese check up wiring
before using in-put
electricity.
|
- If the surface of water reach
E1. motor pump starts to work
automatically, and reach below
E2 Motor pump stop automaticlly. -
While motor is workin, lamp is on. - A
naugty spinning does notoccur, when
the level height is over pump
level. |
KDFS-8PC
(27) Wifing Diagram
Using example in water
supply |
Using example in water
drainage |
|
|
- Conevt to designated terminal
after checking in-put
electricity. - After distributing
wires, plese check up wiring
before using in-put
electricity.
|
- If the surface of water reach
E1. motor pump starts to work
automatically, and reach below
E2 Motor pump stop automaticlly. -
While motor is workin, lamp is on. - A
naugty spinning does notoccur, when the level height is over pump
level. |
|
- After checking up power source, ansd then
connect to designated
termainal. |
|
- Please clean up electrode every six
months. |
|
- Electrode may be mal-functioning, if
disconnection membrane is
formed. |
|
- Sensing distance is accurate by enploying
fixing pad electrode. |
|
- Do not use over-load above standartd at
contacting point of out-put relay.
|
|
- Mal-function may occur when in-put
voltage is over standard
voltage. |
|
- After finishing distributing wires,
Please check up wires before using in-put
electricity. |
|
- Do not use water containing
oil. | |
|